I. 0.6/1KV XLPE Insulated Flame Resistant Power Cable
II. 0.6/1KV PVC Insulated Flame Resistant Power Cable
III. 0.6/1KV XLPE Insulated Fire Retardant Power Cable
IV. PVC Insulated Cable with Rated Voltage up to and including 450/750V
V. pre-fabricated branch plastic insulation cable with a rated voltage of 0.6/1KV
 

pre-fabricated branch plastic insulation cable with a rated voltage of 0.6/1KV
I. Product standard: Enterprise standard
II. Purpose: The product is applicable to 0.6/KV and below power distribution for medium and high-storey residence.
III. Utilization features: Long-term allowable work temperature of cables
Maximum rated temperature 90 ¡ãC of cross-linked polyethylene insulation conductor
Maximum rated temperature 70 ¡ãC of cross-linked polyethylene insulation conductor
IV. Please see Table 1 for the branch cable model.

ÐòºÅ

Cable name

Model

Single core

3-core twisting type
4-core twisting type
5-core twisting type

1

Branch cable of PVC insulation sleeve

FZ-V V

FZ-V V-3
FZ-V V-4
FZ-V V-5

2

Combustion resistant branch cable of PVC insulation sleeve

FZ-ZRV V

FZ-ZRV V-3
FZ-ZRV V-4
FZ-ZRV V-5
3
Refractory branch cable of PVC insulation sleeve
FZ-NHV V
FZ-NHV V-3
FZ-NHV V-4
FZ-NHV V-5
4
Branch cable of cross-linked
polyethylene insulation PVC sleeve
FZ-YJV
FZ-YJV-3
FZ-YJV
FZ-YJV
5
Combustion resistant branch cable of
cross-linked polyethylene insulation PVC sleeve
FZ-ZRYJV
FZ-ZRYJV-3
FZ-ZRYJV-4
FZ-ZRYJV-5

6

Refractory branch cable of cross-linked polyethylene insulation PVC sleeve

FZ-NHYJV

FZ-NHYJV-3
FZ-NHYJV-4
FZ-NHYJV-5
Remark: Section area of main line cable shall be 10-800mm2 while section area of branch cable shall be 6-400mm2.

V. Please see the following table for technological parameters

Nominal section
mm2
External diameter of tight
conductive wire core mm
Insulation thickness
mm
Sleeve thickness
mm
AC test
kv/5min
DC resistance
of 20 maximum conductor
¦¸/km
6
3.1
0.8
1.4
3.5
3.08
10
3.8
1.0
1.4
1.83
16
4.8
1.0
1.4
1.15
25
6.0
1.2
1.4
0.727
35
7.0
1.2
1.4
0.524
50
8.4
1.4
1.4
0.387
70
10.0
1.4
1.4
0.268
95
11.6
1.6
1.5
0.193
120
13.0
1.6
1.6
0.153
150
14.6
1.8
1.8
0.124
185
16.2
2.0
2.0
0.0991
240
18.4
2.2
2.2
0.0754
300
20.8
2.4
2.6
0.0601
400
24.1
2.6
2.6
0.0470
500
26.9
2.8
2.8
0.0366
630
30.2
2.8
2.8
0.0283
800
33.5
2.8
2.8
0.0221

VI. Please see the following table for flow (30¡æ) reference value of single core cables during the laying operation in the air.

Conductor section mm2
XLPE cable A (rated temperature 90¡æ)
PVC cable A (rated temperature 70¡æ)
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
54
75
100
161
201
246
318
389
454
527
605
719
740
847
1013
1190
1527
43
60
80
130
162
197
254
311
362
419
480
569
659
795
920
1020
1413

VII. Laying construction methods
Generally speaking, the pre-fabricated assembly branch cables of vertical main line shall be laid according to the following points:
Place the cable disc on the pay-off stand (the cable disc shall be placed in the downstairs and cables shall be lifted up);
Lifting ropes shall be connected with cables through winding machine;
Start the winding machine and lift up cables;
Once the lifting cable net sleeve has reached the roof, suspend the net sleeve on the prepared hook;
Fix up the middle part;
Connect the branch line end and current meter or circuit breaker;
Connect with the horizontal main line or main circuit board.


VIII. Construction notice
Special attention shall be paid to the following points during the laying of pre-fabricated assembly branch cables:
Confirm the transportation methods (vehicle dimension and parking lot) in advance;
Confirm whether pre-fabricated branch can safely pass the hole;
Adopt preventive measures to prevent branch damage in the holes during lifting operation;
Refrain from imposing tension force on branch during lifting operation;
Utilize lifting cables with above 4 times cable weight;
Consider rainwater shed measures and empty disc disposal measures in advance;
After the cable lifting operation, adopt proper measures for fixation to avoid falling and thus damage; ¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡
It is forbidden to utilize iron clamping tools for single core cables.
¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡

 