¡¡¡¡¡¡¡¡Home¡¡|¡¡Introduction¡¡|¡¡Product¡¡|¡¡Company Honour ¡¡|¡¡Produce equipment¡¡|¡¡Technical Support¡¡|¡¡Production Performance¡¡
 
   
 

KYN1-12£¨2£©Metal-clad Removable Enclosed Switch Cabinet

 


I. General Description
KYN1-12£¨Z£©type metal-clad removable enclosed switch cabinet (called switch cabinet for short). It is applicable for power receiving and distribution in the 3.6-12Kv three-phase AC 50Hz single bus bar and single bus bar sectioning system. It has the functions of controlling, protecting and monitoring the circuit.

II. Operating Environment
a. The Ambient temperature upper limit and lower limit are respectively +40¡æ and -40¡æ; (allowing storage and transportation at -30¡æ);
b. Altitude is not more than 1000m;
c. Relative humidity: daily average value should not be more than 95%, while monthly average value should not be more than 90% (+25¡æ);
d. Seismic intensity should be not more than 8¡ã;
e. Places without fire, explosion risk, serious pollution, chemical corrosion and violent vibration.
III. Type


IV. Design & Structure
The switch cabinet is metal-clad. Its structure design accords with the standards GB3906-91, IEC298, DL404 and DL402. The crust structure is made of steel plates by means of bending and welding, which are joined by bolts. The hand buggy panel is the door of cabinet. The bosom of switch cabinet is divided into a breaker chamber, a main bus bar chamber, a cable chamber and a relay chamber by metal partitions. The degree of protection of the entire crust and compartments is IP2X equally. All the metal structures are connected to ground reliably. All the compartments of main circuit system have pressure release channels for independent exhaust.


V. Main technical parameters of switch cabinet

Serial No.

Name

Unit

Data

1

Rated voltage

KV

3.6¡¡7.2¡¡12

2

Rated current

A

1000¡¡1250¡¡1600¡¡2500

3

Rated frequency

Hz

50

4

Rated short-time withstand current

KA

20¡¡31.5¡¡40

5

Rated peak withstand current

KA

50¡¡80¡¡100

6

Rated power frequency withstand current

KV

42(1min)

7

Rated lightning impulse withstand current

KV

75

8

Rated short circuit period

S

4

9

Degree of protection

 

IP2X

10

Weight

Kg

800

11

Overall dimension (width*depth* height)

mm

840*1500(1650)*2280
1000*1500(1800)*2280


VI. Ordering Instructions
The purchaser should supply following information for ordering.
a. Scheme of primary circuit
b. Types and specifications of electric components in the switchgear;
c. Material quality and specifications of main bus bar and branch bus bar (according to the manufactory¡¯s standards if not specified);
d. Schematic diagram of small wiring or standard schematic diagram, miniature bus bar array diagram and terminal diagram;
e. Coating color of switchgear;
f. Names and quantity of spare parts
g. Please negotiate with the manufacturer on special requirements.
   
Coslight Group Harbin Switch Co., Ltd
Address: No. 68, Dianlan Street, Xuefu Road, Nangang District, Harbin City
Tel£º0451-86661821 / 86661386¡¡¡¡Fax£º0451-86662333